- Schneider Electric Altistart 22
- to clear faults press 'up arrow + down arrow + ENT' simultaneously
- 'SSCr' error: no current detected (unwired)
- 'OLF' error: overload fault
- Allow the motor to cool and the ATS22 to timeout 10-15minutes before resetting the fault
- Check the ACC and tHP settings in the SET menu. If appropriate, increase either/both.